![]() |
| Switchgear and Protection |
1. Short-circuit currents are due to________.
a. Single-phase to earth
fault
b. Phase-to-phase fault
c. All the three phases-to
earth fault
d. All the three-phases
short-circuited
e. Any of the above
2. The most serious
consequence of a major uncleared short-circuit fault could be________.
a. Blowing of fuse
b. Fire
c. Heavy voltage drop
d. None of the above
3. Which of the following
results in a symmetrical fault?
a. Single-phase to earth
b. Phase-to-phase
c. All the three phases to earth
d. Two phases to earth
4. Which portion of the
transmission system is more prone to faults?
a. Underground cable
b. Overhead lines
c. Transformer
d. Alternator
5. Which portion of the
power system is least prone to faults?
a. Overhead lines
b. Transformers
c. Switchgear
d. Alternators
6. The magnitude of fault
current depends upon________.
a. Total impedance up to
fault
b. Voltage at the fault
point
c. Load current being
supplied before occurrence of fault
d. Both (a) and (b)
7. The most common type of
fault is________.
a. Single-phase to ground
b. Phase-to-phase
c. Two-phase to ground
d. Three-phase to ground
8. The maximum short-circuit
occurs in the case of__________.
a. Single-line-to-ground
fault
b. Line-to-line fault
c. Double-line-to-ground
fault
d. Three-phase bolted fault
9. For a fault at the
terminals of a synchronous generator, the fault current is maximum for a________.
a. 3-phase fault
b. 3-phase to ground fault
c. Line-to-ground fault
d. Line-to-line fault
10. A 10 kVA, 400 V/200 V
single-phase transformer with 10% impedance, draws a steady short-circuit
current of_______.
a. 50 A
b. 150 A
c. 250 A
d. 350 A
11. A transformer rated for
500 kVA, 110 kV/0.4 kV has an impedance of 10% and is connected to an infinite
bus. The fault level of the transformer is________.
a. 500 kVA
b. 5000 kVA
c. 500 MVA
d. None of these
12. Series reactors are used
to_______.
a. Bring down the fault level withing the capacity of the switchgear
b. Improve the voltage
regulation
c. Improve the power factor
of the power system
d. Improve the transmission
efficiency
13. Current limiting
reactors maybe________.
a. Air-cooled air-cooled
b. Oil immersed magnetically
shielded
c. Oil immersed
non-magnetically shielded
d. Any of the above
14. The symmetrical
components are used in the fault analysis because________.
a. The number of equations
becomes smaller
b. The sequence networks do not have mutual couplings
c. The results are required
in terms of symmetrical components
15. In a star-connected system
without neutral grounding, zero-sequence currents are_______.
a. Zero
b. Phasor sum of phase
currents
c. Same as rms value of
phase currents
d. Same as peak value of
phase currents
16. A balanced 3-phase
system consists of_______.
a. Zero-sequence currents
only
b. Positive-sequence currents only
c. Negative-and
zero-sequence currents
d. Zero, negative and
positive sequence currents
17. The positive sequence
current of a transmission line is___________.
a. Always zero
b. 1/3 of negative sequence
current
c. Equal to negative sequence current
d. 3 times negative sequence
current
18. In case of an unbalanced
star-connected load supplied from an unbalanced 3-phase, 3-wire system, load
currents will consist of _________.
a. Posistive-sequence
components
b. Negative-sequence
components
c. Zero sequence components
d. Only (a) and (b)
19. For an unbalanced fault,
with paths for zero-sequence currents, at the point of a fault______.
a. The negative and zero
sequence voltages are minimum
b. The negative and zero sequence voltages are maximum
c. The negative sequence
voltage is minimum and zero sequence voltage is maximum
d. The negative sequence
voltage is maximum and zero sequence voltage is minimum
20. Zero sequence fault
current is absent when fault is_______.
a. Single-line to ground
fault
b. Line-to-line ground fault
c. Double-line to ground
fault
d. Line-to-line
21. The current of a
single-phase load drawn from a 3-phase system has_________.
a. Zero-sequence component
of current as zero
b. Negative sequence
component of current more than positive sequence component
c. Positive, negative and zero sequence components equal
d. Negative sequence
component of current less than positive sequence component
22. Zero sequence currents
can flow from a line to transformer bank
if the windings are in______.
a. Delta/delta
b. Star/Grounded star
c. Delta/star
d. Grounded star/delta
23. Negative sequence
reactance of a transformer is_________.
a. Smaller than the positive
sequence reactance
b. Larger than the positive
sequence reactance
c. Equal to the positive sequence reactance
24. If all the sequence
voltages at the fault point in a power system are equal, then the fault is
a_________.
a. Double-line to ground fault
b. Line-to-line fault
c. Line-to ground fault
d. Three-phase fault
25. Fuses have got
advantages of________.
a. Cheapest type of
protection
b. Inverse time current
characteristic
c. No maintenance
d. Current limiting effect
under short-circuit conditions
e. All of the above


0 Comments
If you have any doubt, feel free to ask.